Specification
Meets ANSI/EIA/TIA 568-B.2 requirements
Meets general purpose cable UL-1581 CM rating
Meets fire retardant low smoke IEC60332-1 rating
Meets plenum UL-910 rating
Description
Unshielded Copper cable, 4 pairs, category 5e, solid
Cable is used for indoor installation

| Electrical Characteristic | |||||||
| Frequency, MHz | RL | Attenuation, dB | NEXT, dB | PSNEXT, dB | ELFEXT, dB | PSELFEXT, dB | |
| 0.772 |
- | 1.8 | 67.0 | 64.0 | - | - | |
| 1.0 | 20.0 | 2.0 | 65.3 | 62.3 | 63.8 | 60.8 | |
| 4.0 | 23.0 | 4.0 | 56.3 | 53.3 | 51.7 | 48.7 | |
| 8.0 | 24.5 | 5.8 | 51.8 | 48.8 | 45.7 | 42.7 | |
| 10.0 | 25.0 | 6.5 | 50.3 | 47.3 | 43.8 | 40.8 | |
| 16.0 | 25.0 | 8.2 | 47.3 | 44.3 | 39.7 | 36.7 | |
| 20.0 | 25.0 | 9.3 | 45.8 | 42.8 | 37.7 | 34.7 | |
| 25.0 | 24.3 | 10.4 | 44.3 | 41.3 | 35.8 | 32.8 | |
| 31.25 | 23.6 | 11.7 | 42.9 | 39.9 | 33.9 | 30.9 | |
| 62.5 | 21.5 | 17.0 | 38.4 | 35.4 | 27.8 | 24.8 | |
| 100.0 | 20.1 | 22.0 | 35.3 | 32.3 | 23.8 | 20.8 | |
| Conductor resistance at 20°C (68°F) | 9.38Ω/100m (2.9Ω/100ft) | |
| DC Resistance Unbalance | 5% | |
| Pair-to-Ground Capacitance Unbalance | 330pF/100m (101pF/100ft) | |
| Impedance 0.772-100 MHz | 85Ω-115Ω | |
| Mutual Capacitance | 5.6nF/m (1.7nF/ft) | |
| Spark Test | 2.5kV |